ICA UPS SE2000 Capacity 2000VA. Because the UPS is the true on-line system, conditioned power is provided continuously to the attached load. The UPS constantly regulates and filter the AC input voltage and supply a clean and stable AC voltage to the output and charge the batteries. When the AC input voltage low or loss, the UPS protects the load instantaneously and supply a stable AC voltage without any transfer time.
TECHNICAL INFORMATION :
Description | : | UPS SE2000 |
Capacity | : | 2000 VA / 1400 W |
AC Voltage | : | 110 ~ 285 V |
: | 160 ~ 285 V | |
AC Frequency | : | 50 ± 5 Hz |
AC Protection | : | 12 A |
DC Voltage | : | 96 V |
DC INT Battery | : | 8 x 12 V, 7 Ah |
DC Protection | : | FUSE |
CHG Topology | : | SWITCHING REGULATION |
CHG Floating Voltage | : | 108.8 V |
INV Wave Form | : | SINEWAVE |
INV Distorsion | : | < 3% THD |
INV Topology | : | PULSE WIDTH MODULATION (PWM) |
INV Voltage | : | 220 ± 1% V |
INV Frequency | : | 50 ± 1% Hz |
INV Efficiency | : | > 85% |
Transfer Time When AC In Loss | : | 0 ms |
Transfer Time STS | : | 2 ms Inverter to Bypass, 0 ms Back To Inverter |
Back Up Time | : | 10 min |
BZR AC Input Abnormall | : | INTERMITTENT SOUND WITH 4 SECONDS INTERVAL |
BZR Battery Low | : | INTERMITTENT SOUND WITH 1 SECONDS INTERVAL |
Opera Temp | : | 0 – 40 °C |
Dimension(DxWxH) | : | 470 x 191 x 338 mm |
Weight | : | 35 Kg |